Web Datalogger Unit Detailed Version-Up Information

Version-up Information

Version-Up Information(Ver.2.58 to Ver.2.60)

The following points have been upgraded.

  • In mail function, fixed the problem that the attached file might not be sent correctly.
  • In mail function, fixed the problem that the authentication might not be correctly executed in case of SMTP AUTH.

Version-Up Information(Ver.2.50 to Ver.2.58)

The following points have been upgraded.

  • IP address and subnet mask combination have the following limitations.
    IP Address: 0.0.0.1 - 127.255.255.255 => Subnet Mask: 255.0.0.0 - 255.255.255.255
    IP Address: 128.0.0.0 - 191.255.255.255 => Subnet Mask: 255.255.0.0 - 255.255.255.255
    IP Address: 192.0.0.0 - 255.255.255.255 => Subnet Mask: 255.255.255.0 - 255.255.255.255
  • Fixed the problem that trigger was not occurred if the trigger type is [Register], target is [Main Unit] and the data format is [Real Number].
  • E mark of real number became possible to select in the CSV file.
  • Supported the SMTP-AUTH authentication in Mail Transmission Settings.
  • Fixed the problem that there is a little margin of error if the converted value is more than 6 figures.
  • Fixed the problem that if [OR] is selected in trigger and reload the page, [OR] was changed to [AND].
  • Fixed the problem that communication error was occurred if the trigger is PLC contact.
  • Fixed the problem that the wrong time and date data may be recorded.
  • Fixed the problem that the converted value became negative although the data type is unsigned.
    (If the “Conversion Parameter” is 0.1 or 0.01, it’s no problem)

Version-Up Information(Ver.2.42 to Ver.2.50)

The following points have been upgraded.

  • When the mode is changed from RUN to PROG, the “Pulse” or “Difference” value is cleared in case of “Not make the [_MOD] file” mode.
    (These values should not be cleared)
  • “[_ERR] file” is created if the memory is very few.
  • Sometimes there is a broken data in the attached file of e-mail.
  • If there is no log-in condition, the 404 error is occurred during HTTP transferring.
  • The limited account user can use FTP function.
    (FTP connection should not be valid if the user account is limited)
  • The transmission interval of the reading command can be changed.
  • If communication error is occurred during gathering data, the corresponding unit number of internal relay is set to ON.
    (COM1:R4330 – R442F, COM2:R4430 – R452F)
  • “0” or “24” can be selected when the time is AM0:00 in CSV file.
  • The conversion parameter’s available range is expanded from “-9999.99 to 9999.99” to “-9999.999 to 9999.999”.
  • “Ping” is sent to default gateway when the DLU is started or network setting is changed so that the switching HUB can detect the DLU smoothly.
  • TCP protocol port number can be changed.
  • Changed the specification that fixed cycle trigger’s combination is not available.