Rating |
Operating voltage |
100 to 240 V AC, 24 V AC |
12 to 24 V DC, 24 V AC |
100 to 240V AC, 24 V AC |
12 to 24 V DC, 24 V AC |
Frequency |
50/60 Hz common |
-
| 50/60 Hz common |
-
|
Power consumption |
Max. 10 V A |
Max. 3 W |
Max. 10 V A |
Max. 3 W |
Control capacity (resistive) |
5 A, 250 V AC (Resistive load) |
100 mA, 30 V DC |
Time range |
99.99 s, 999.9 s, 9999 s, 99 min 59 s, 999.9 min. 99 h 59 min, 999.9 h (selected by DIP switch) |
Time counting direction |
Addition (UP)/Subtraction (DOWN)
(2 directions selectable by DIP switch) |
Operation mode |
Pulse input: Delayed one shot, OFF-start flicker or ON-start flicker Integrating input: Delayed one shot, OFF-start flicker or ON-start flicker |
Signal/Reset/Stop input |
Min. input signal width: 1 ms, 20 ms (2 directions by selected by DIP switch) |
Lock input |
Min. input signal width: 20 ms |
Input signal |
Open collector input Input impedance: Max. 1 kohm; Residual voltage: Max. 2V Open impedance: 100 kohm or less, Max. energized voltage: 40 V DC |
Indication |
7-segment LCD, Elapsed value (backlight red LED), Setting value (backlight yellow LED) |
Power failure memory method |
EEP-ROM (Min. 105overwriting) |
Time accuracy (max.) |
Operating time fluctuation |
±(0.005%+50 ms) in case of power on start ±(0.005%+20 ms) in case of reset or input signal start [Operating voltage: 85 to 110% Temperature: -10 to +55°C +14 to +131 ° F Min. input signal width: 1ms] |
Temperature error |
Voltage error |
Setting error |
Contact |
Contact arrangement |
Timed-out 1 Form C |
Timed-out 1 Form A (Open collector) |
Initial contact resistance |
100 mohm (at 1 A 6 V DC) |
-
|
Contact material |
Ag alloy/Au flash |
-
|
Life |
Mechanical |
2.0 × 107ope. (Except for switch operation parts) |
-
|
Electrical |
1.0 × 105ope. (At rated control voltage) |
1.0 × 107ope. (At rated control voltage) |
Electrical |
Operating voltage range |
85 to 110% of rated operating voltage |
Initial breakdown voltage |
2, 000 Vrms for 1 min: Between live and dead metal parts (11-pin)
2, 000 Vrms for 1 min: Between input and output 1, 000 Vrms for 1 min: Between contacts |
2, 000 Vrms for 1 min: Between live and dead metal parts (Pin type)
2, 000 Vrms for 1 min: Between input and output |
Initial insulation resistance (At 500 V DC) |
Min. 100 Mohm: Between live and dead metal parts Between input and output Between contacts |
Min. 100 Mohm: Between live and dead metal parts Between input and output |
Operating voltage reset time |
Max. 0.5 s |
Temperature rise |
Max 65°C (under the flow of nominal operating current at nominal voltage) |
Mechanical |
Vibration resistance |
Functional |
10 to 55 Hz: 1 cycle/ min single amplitude of 0.35 mm .014 inch (10 min on 3 axes) |
Destructive |
10 to 55 Hz: 1 cycle/ min single amplitude of 0.75 mm .030 inch (1 h on 3 axes) |
Shock resistance |
Functional |
Min. 98 m 321.522 ft./s2(4 times on 3 axes) |
Destructive |
Min. 294 m 964.567 ft./s2(5 times on 3 axes) |
Operating conditions |
Ambient temperature |
-10°C to 55°C + 14 ° F to + 131 ° F |
Ambient humidity |
Max. 85% RH |
Air pressure |
860 to 1, 060 h Pa |
Ripple rate |
-
| 20% or less |
-
| 20% or less |
Connection |
8-pin/11-pin/screw terminal |
Protective construction |
IP66 (front panel with rubber gasket) |